Series#: Valve Positioner -> ABB -> TZIDC
ABB V18345-1010421001 TZIDC Electro-Pneumatica Positioner
Magnam inventarium habemus pro serie valvae ABB TZIDC positorium, ATEX-certificatum positionem electro-pneumaticam, V18345 seriem positionem intelligentes et accessiones affinis.
100% Original and new, In stock by Eaton Company.
Delivery time: Ready in stock and 1 days for ship out
MOQ: 1pcs
| Availability: | |
|---|---|
V18345-1010421001
ABB
ABB V18345-1010421001 est valvae electronico-pneumaticae positionem intelligentem ATEX-pneumaticum e seriei TZIDC conformatum pro actuatoribus duplicatis cum functione deficiente et ad 4-20mA analogi positionem feedback conformata. ATEX Ex ib IIC T6 certificatio idoneum facit ad usum atmosphaerarum explosivae potentia (Zone 1/2). Cum auto-calibratione, sub-0.5% accuratione, et IP65 aluminii habitationi, late explicat in processu olei et gasi, plantae chemicae, refinerias, et fabricam pharmaceuticam, ubi utraque cura moderatio et explosio tutelae requiruntur.
Feature |
Specification |
|---|---|
Manufacturer |
ABB |
Exemplar Number |
V18345-1010421001 |
Product Series |
TZIDC intelligentes Positioner |
habitationem |
Aluminium, IP65 / NEMA 4X |
Actuator Type |
Duplex agens |
Tutus Modus Fail- |
Securus non (potestatis iactura movet tutos) |
Input signum |
4-20mA, duo filum |
Communicationis |
HART capax (per obturaculum-in moduli) |
Praesidium explosio |
ATEX Ex ib IIC T6 |
Module videre |
Analog 4-20mA situ obturaculum-in feedback |
hospites |
Cable: 1/2-14 NPT, Air: 1/4-18 NPT |
Supple Pressura |
1.4-6 bar (20-90 psi) |
Air Consumptio |
< 0.03 kg/h |
Air Capacity @ 1.4 bar |
~5.0 kg/h (2.3 scfm) |
Air Capacity @ 6 bar |
~13 kg/h (6.0 scfm) |
Travel Range (Linear) |
20-150 mm |
Iter dolor (Rotary) |
25°-120° (libitum 270°) |
Proprium Deviationis |
≤ 0.5% |
Mortuus Band |
Product 0.1% -10% |
Resolution |
> 4,000 digital steps |
Sample Rate |
20 ms |
Temperatus Drift |
≤ 0.5% per 10°C |
Ambiens Temperature |
-40°C ad +85°C |
Vibratio Resistentia |
±1% ad 10g / 80Hz |
Seismic Rating |
DIN/IEC 68-3-3 Classis III |
Adscendens Standard |
DIN/IEC 534 / NAMUR (linearia), VDI/VDE 3845 (in gyro) |
Curvae propriae |
Linearibus centesimae aequalis (1:25/1:50/25:1/50:1), user definitae (20 puncta) |
Pondus |
~1.7 kg |
Q: Quid est ABB V18345-10100421001?
A: The V18345-1010421001 est ATEX-certificatum TZIDC valvae positio intelligentis electro-pneumaticae configuratus pro actuatoribus duplicatis agentium cum functione et analogia positionis deficientis feedback.
Q: Quid ATEX certificatione hoc exemplum habet?
A: Certum est ATEX Ex ib IIC T6, idoneum ad institutionem in Zona 1 et in Zona 2 ancipitia areae ubi adsint atmosphaerae gas explosivae.
Q: Quid est medium?
A: Duplex agens significat utrobique moderatur actus piston. Deficient-tutum significat quod, amissione electrica potentiae vel signo, positio plectrum agit ad statum tutum (plene clausum vel plene apertum), criticum ad applicationes shutdown tutandas.
Q: Quomodo hoc differt a V18345-10100521001?
A: The key difference is position 4 (explosion protection) and situs 5 (output/tutus position). 1010421001 ATEX certificationem et operationem deficientem habet; the 1010521001 nullam habet explosionem tutelam et operationem deficientem.