Availability: | |
---|---|
Mitsubishi PLC Module FX1N-24MT-001/FX1N-24MR-001
Mitsubishi PLC Module FX1N | Specification | Remarks |
Operation control method | Cyclic operation by stored program | |
I/O control method | Batch processing method (when END instruction is executed) | I/O refresh instruction is available |
Operation processing time | Basic instructions: 0.55 to 0.7 ms Applied instructions: 1.65 to several 100 ms | |
Programming language | Relay symbolic language + step ladder | Step ladder can be used to produce an SFC style program |
Program capacity | 8K steps | Provided by built in EEPROM memory |
Number of instructions | Basic sequence instructions: 29 Step ladder instructions: 2 Applied instructions: 89 | A Maximum 120 applied instructions are available including all variations |
I/O configuration | Max hardware I/O configuration points 128, dependent on user selection (Max. software addressable Inputs 128, Outputs 128) |
State relays (S coils) Latched | 1000 points | S0 to S999 |
State relays (S coils) Initial | 10 points (subset) | S0 to S9 |
Timers (T) 100 msec | Range: 0 to 3,276.7 sec 200 points | T0 to T199 |
Timers (T) 10 msec | Range: 0 to 327.67 sec 46 points | T200 to T245 |
Timers (T) 1 msec | Range: 0 to 32.767 sec 4 point | T246 to T249 |
Timers (T) 100 msec retentive | Range: 0 to 3,276.7 sec 6 points | T250 to T255 |
Counters (C) General | Range: 1 to 32,767 counts 16 points | C0 to C15 Type: 16 bit up counter |
Latched | 184 points (subset) | C16 to C199 Type: 16 bit up counter |
General | Range: 1 to 32,767 counts 20 points | C200 to C219 Type: 32 bit bi-directional counter |
Latched | 15 points (subset) | C220 to C234 Type: 32 bit bi-directional counter |
High speed counters (C) 1 phase | Range: -2,147,483,648 to +2,147,483,647 counts Select upto four 1 phase counters with a combined counting frequency of 5kHz or less. Alternatively select one 2 phase or A/B phase counter with a counting fre- quency of 2kHz or less. Note all counters are latched | C235 to C240 6 points |
1 phase c/w start stop input | C241, C242 and C244 3 points | |
2 phase | C246, C247 and C249 3 points | |
A/B phase | C251, C252 and C254 3 points | |
General | 7128 points | D0 to D127 & D1000 to D7999 Type: 16 bit data storage register pair for 32 bit device |
Latched | 872 points (subset) | D128 to D999 Type: 16 bit data storage register pair for 32 bit device |
File | 7000 points | D1000 to D6999 set by parameter in 3 blocks of 500 program steps Type: 16 bit data storage register |
Externally adjusted | Range: 0 to 255 2 points | Data is move from external setting potentiometers to registers D8030 and D8031) |
Special | 256 points (inclusive of D8013, D8030 and D8031) | From the range D8000 to D8255 Type: 16 bit data storage register |
Index | 16 points | V and Z Type: 16 bit data storage register |
Pointers with CALL | 128 points | P0 to P127 |
For use with interrupts | 6 points | I00❑ to I30❑ (rising trigger ❑ = 1, falling trigger ❑ = 0) |
Nest levels | 8 points for use with MC and MCR | N0 to N7 |
Decimal K | 16 bit: -32,768 to +32,767 32 bit: -2,147,483,648 to +2,147,483,647 | |
Hexadeci- mal H | 16 bit: 0000 to FFFF 32 bit: 00000000 to FFFFFFFF |