| Availability: | |
|---|---|
Omron PLC CP series CP1L CPU Unit CP1L-M30DR-A CP1L-M30DT-A
CP1L-EM” and “CP1L-EL” have complete with a Ethernet
Omron PLC Controller Module CP-series
At Coberry we can provide you with a brand Factory new covered by the Original Manufacturers Warra
Buying a Used Parts can offer great savings over brand new
Buying a refurbished can offer great savings over brand new
| Models | CP1L-M60(60 points) | CP1L-M40(40 points) | CP1L-M30(30 points) | CP1L-L20(20 points) | CP1L-L14(14 points) | CP1L-L10(10 points) |
| CP1L-M60@@–@ | CP1L-M40@@–@ | CP1L-M30@@–@ | CP1L-L20@@–@ | CP1L-L14@@–@ | CP1L-L10@@–@ | |
| Control method | Stored program method | |||||
| I/O control method | Cyclic scan with immediate refreshing | |||||
| Program language | Ladder diagram | |||||
| Function blocks | Maximum number of function block definitions: 128 Maximum number of instances: 256 Languages usable in function block definitions: Ladder diagrams, structured text (ST) | |||||
| Instruction length | 1 to 7 steps per instruction | |||||
| Instructions | Approx. 500 (function codes: 3 digits) | |||||
| Instruction execution time | Basic instructions: 0.55 ms min. Special instructions: 4.1 ms min. | |||||
| Common processing time | 0.4 ms | |||||
| Program capacity | 10K steps | 5K steps | ||||
| Number of tasks | 288 (32 cyclic tasks and 256 interrupt tasks) | |||||
| Maximum subroutine number | 256 | |||||
| Maximum jump number | 256 | |||||
| Work bits | 8,192 bits (512 words): W000.00 to W511.15 (W0 to W511)CIO Area: 37,504 bits (2,344 words): CIO 3800.00 to CIO 6143.15 (CIO 3800 to CIO 6143) | |||||
| TR Area | 16 bits: TR0 to TR15 | |||||
| Holding Area | 8,192 bits (512 words): H0.00 to H511.15 (H0 to H511) | |||||
| AR Area | Read-only (Write-prohibited): 7168 bits (448 words): A0.00 to A447.15 (A0 to A447) Read/Write: 8192 bits (512 words): A448.00 to A959.15 (A448 to A959) | |||||
| Timers | 4,096 timer numbers: T0 to T4095 | |||||
| Counters | 4,096 counter numbers: C0 to C4095 | |||||
| DM Area | 32 Kwords: D0 to D32767 | 10 Kwords: D0 to D9999, D32000 to D32767 | ||||
| Data Register Area | 16 registers (16 bits): DR0 to DR15 | |||||
| Index Register Area | 16 registers (32 bits): IR0 to IR15 | |||||
| Task Flag Area | 32 flags (32 bits): TK0000 to TK0031 | |||||
| Trace Memory | 4,000 words (500 samples for the trace data maximum of 31 bits and 6 words.) | |||||
| Memory Cassette | A special Memory Cassette (CP1W-ME05M) can be mounted. Note: Can be used for program backups and auto-booting. | |||||
| Clock function | Supported. Accuracy (monthly deviation): -4.5 min to -0.5 min (ambient temperature: 55°C),-2.0 min to +2.0 min (ambient temperature: 25°C), -2.5 min to +1.5 min (ambient temperature: 0°C) | |||||
| Memory backup | Flash memory: User programs, parameters (such as the PLC Setup), comment data, and the entire DM Area can be saved to flash memory as initial values.Battery backup: The Holding Area, DM Area, and counter values (flags, PV) are backed up by a battery. | |||||
| Battery service life | Service life expectancy is 5 years at 25°C, less at higher temperatures. (From 0.75 to 5 years depending on model, power supply rate, and ambient temperature.) | |||||