Item | CS1W-DA041 | CS1W-DA08V | CS1W-DA08C | ||
Applicable PLC model | CS series | ||||
Unit type | CS1 Special I/O Unit | ||||
Isolation *1 | Between I/O and PLC signals: Photocoupler (No isolation between individual I/O signals.) | ||||
External terminals | 21-point detachable terminal block (M3 screws) | ||||
Power consumption | 130 mA max. at 5 VDC, 180 mA max. at 26 VDC | 130 mA max. at 5 VDC, 180 mA max. at 26 VDC | 130 mA max. at 5 VDC, 250 mA max. at 26 VDC | ||
Dimensions (mm) *2 | 35 ´ 130 ´ 126 (W ´ H ´ D) | ||||
Weight | 450 g max. | ||||
General specifications | Conforms to general specifications for SYSMAC CS-series Series. | ||||
Mounting position | CS-series CPU Rack or CS-series Expansion Rack (Cannot be mounted to a C200H Expansion I/O Rack or a SYSMAC BUS Slave Rack.) | ||||
Maximum number of Units | Depends on the Power Supply Unit. *3 | ||||
Data exchange with CPU Units *4 | Special I/O Unit Area CIO 200000 to CIO 295915 (Words CIO 2000 to CIO 2959) | ||||
Internal Special I/O Unit DM Area (D20000 to D29599) | |||||
Number of analog outputs | 4 | 8 | 8 | ||
Output signal ranges *5 | 1 to 5 V/4 to 20 mA 0 to 5 V 0 to 10 V -10 to 10V | 1 to 5 V 0 to 5 V 0 to 10 V -10 to 10 V | 4 to 20 mA | ||
Output impedance | 0.5 Ω max. (for voltage output) | ||||
Max. output current (for 1 point) | 12 mA (for voltage output) | ||||
Maximum permissible load resistance | 600 Ω (current output) *9 | – | 600 Ω (current output) *8 | ||
Resolution | 4,000 (full scale) | ||||
Set data | 16-bit binary data | ||||
Accuracy *6 | 23±2°C: | Voltage output: ±0.3% of full scale Current output: ±0.5% of full scale | |||
0°C to 55°C: Voltage output: ±0.5% of full scale Current output: ±0.8% of full scale | |||||
D/A conversion time *7 | 1.0 ms/point max. | ||||
Output functions |
Output hold function | Outputs the specified output status (CLR, HOLD, or MAX) under any of the following circumstances. When the Conversion Enable Bit is OFF. *8 In adjustment mode, when a value other than the output number is output during adjustment. When there is an output setting error or a fatal error occurs at the PLC. When the CPU Unit is on standby. When the Load is OFF. |