Part Number | AJ65SBTB2N-8R |
Number of output points | 8 points |
Insulation method | Relay |
Rated load voltage×current | 24 V DC (resistive load), 240 V AC (cosf = 1)/ 2 A/point 4 A/common |
Min. switching load | 5 V DC 1 mA |
Max. switching voltage | 264 V AC 125 V DC |
Max. switching frequency | 3600 times/hour |
Surge suppression | None |
Common method | 8 points/1 common (terminal block 2-wire type) |
Number of stations occupied | 1 station 32 points assignment (use 8 points) |
Noise durability | Simulator noise 1500 Vp-p, noise width 1 ms, noise carrier frequency 25 to 60 Hz (noise simulator condition) Fast transient/noise burst IEC61000-4-4 : 1 kV |
Withstand voltage | 2830 V AC between all AC external terminals and ground, rms/ 3 cycles (2000 m above sea level) 500 V AC for 1 minutes between all DC external terminals and ground |
Insulation resistance | 10 M W or higher, measured with a 500 V DC insulation resistance tester between all AC external terminals and ground 10 M W or higher, measured with a 500 V DC insulation resistance tester between all DC external terminals and ground |
Weight (kg) (lb.) | 0.25 (0.55) |
External connection method | 7-point 2-piece terminal block (transmission circuit, module power supply terminal), Direct-type 18-point terminal block (I/O power supply area) (M3 screw) |
Applicable solderless terminal | • RAV1.25-3.5 (in conformance with J2IS C 2805) [Applicable wire size: 0.3 to1.25 mm ] • V2-MS3 (Japan Solderless Terminal Mfg. Co., Ltd.), RAP2-3S RAP2-3 (Japan Terminal Co., Ltd.) • 2-3N, 2-3S (NICHIFU TERMINAL IN2DUSTRIES Co., Ltd.) [Applicable wire size: 1.25 to 2 mm ] |
Part Number | AJ65SBTB2N-16R |
Number of output points | 16 points |
Insulation method | Relay |
Rated load voltage×current | 24 V DC (resistive load), 240 V AC (cosf = 1)/ 2 A/point 8 A/1 common |
Min. switching load | 5 V DC 1 mA |
Max. switching voltage | 264 V AC 125 V DC |
Max. switching frequency | 3600 times/hour |
Surge suppression | None |
Common method | 16 points/1 common (terminal block 2-wire type) |
Number of stations occupied | 1 station 32 points assignment (use 16 points) |
Noise durability | Simulator noise 1500 Vp-p, noise width 1 ms, noise carrier frequency 25 to 60 Hz (noise simulator condition) Fast transient/noise burst IEC61000-4-4 : 1 kV |
Withstand voltage | 2830 V AC between all AC external terminals and ground, rms/ 3 cycles (2000 m above sea level) 500 V AC for 1 minutes between all DC external terminals and ground |
Insulation resistance | 10 M W or higher, measured with a 500 V DC insulation resistance tester between all AC external terminals and ground 10 M W or higher, measured with a 500 V DC insulation resistance tester between all DC external terminals and ground |
Weight (kg) (lb.) | 0.35 (0.77) |
External wiring system | 7-point 2-piece terminal block (transmission circuit, module power supply terminal), Direct-type 34-point terminal block (I/O power supply area) (M3 screw) |
Applicable solderless terminal | • RAV1.25-3.5 (in conformance with JIS-C2805) [Applicable wire size: 0.3 to1.25 mm2] • V2-MS3 (Japan Solderless Terminal Mfg. Co., Ltd.), RAP2-3S RAP2-3 (Japan Terminal Co., Ltd.) 2-3N, 2-3S (NICHIFU TERMINAL INDUSTRIES Co., Ltd.) [Applicable wire size: 1.25 to 2 mm2] |