| Availability: | |
|---|---|
6DL1134-6GH00-0PH1
Siemens
The Siemens SIMATIC ET 200SP HA IM 134-6 GH (6DL1134-6GH00-0PH1) is a PROFINET IO interface module serving as the head station for the ET 200SP High Availability distributed I/O system. It provides the communication gateway between the I/O modules and the PROFINET network, enabling high-speed data exchange with S7-410 series controllers. The module supports HSR (High Speed Redundancy) for seamless failover in redundant controller configurations. Typical deployment involves pairing two IM 134-6 GH modules with two S7-410 CPUs to achieve true high availability. Essential for process automation applications in oil & gas, chemical, and power generation industries where continuous operation and zero downtime are critical requirements.
Q: What is the primary function of this module?
A: It serves as the PROFINET IO interface (head station) connecting the ET 200SP HA I/O station to the PROFINET network.
Q: Does this module support redundancy?
A: Yes, it supports HSR (High Speed Redundancy) when paired with two S7-410 CPUs.
Q: What controllers is it compatible with?
A: It is designed to work with S7-410 series controllers in process automation.
Q: Is a specific BaseUnit required?
A: Yes, an ET 200SP HA specific Base Unit is required. Standard Base Units are not compatible.
Q: Can it be used with standard ET 200SP I/O modules?
A: No. It is designed exclusively for ET 200SP HA (High Availability) I/O modules
FAQ
.
Siemens 6DL1134-6GH00-0PH1 | |
SIMATIC ET 200SP HA | AI 16xI 2-wire HA, suitable for terminal block H1, P0, CC01, channel diagnostics | |
Feature | Specification |
Product type designation | AI 16xI 2-wire HA |
Firmware version | V1.0 |
FW update possible | Yes |
Usable terminal block | type H1, N0, H0 |
Color code for module-specific color-coded label | CC01 |
I&M data | Yes; I&M0 to I&M3 |
Engineering with STEP 7 TIA Portal | V18 |
Rated supply voltage (DC) | 24 V |
Permissible range, lower limit (DC) | 19.2 V |
Permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Current consumption (rated value) | 350 mA |
Number of analog inputs for current measurement | 16 |
Input ranges (rated values), 0 to 20 mA | Yes; 16 bit incl. sign |
Input ranges (rated values), 4 mA to 20 mA | Yes; 16 bit incl. sign |
Input resistance (4 mA to 20 mA) | 250 ohm |
Cycle time (all channels), min. | 400 ms |
Measurement principle | Integrating (Sigma-Delta) |
Integration time, parameterizable | Yes; 16.6 / 20 / 100 ms |
Basic error limit at 25 °C, current | 0.3 % |
Operational error limit overall temperature range, current | 0.5 % |
Linearity error | 0.01 % |
Temperature error | 0.005 %/K |
Encoder supply 24 V | Yes; short-circuit protection |
Diagnostic alarm | Yes |
Wire break | Yes; channel-by-channel, at 4 to 20 mA only |
DIAG LED | Yes; green/red |
Channel status display | Yes; green LED |
Potential separation between channels and backplane bus | Yes |
Isolation tested with | 1500 V DC/1 min, type test |
Ambient temperature horizontal installation | -40 to 70 °C |
Width | 22.5 mm |
Height | 115 mm |
Depth | 138 mm |
Weight, approx. | 148 g |
autocoberry.com — We supply whatever you need, with the price far lower than the market rates. | |