The Siemens SIMATIC ET 200SP HA DQ 8x24V DC/2A HA (6DL1134-6TB00-0HX1) is an 8-channel digital output module for the ET 200SP High Availability distributed I/O system. Each channel provides 24V DC output at 2A maximum current with electronic switching. The module features comprehensive per-channel diagnostics and supports redundant H-System configurations with S7-410 controllers. Designed for controlling solenoid valves, actuators, relays, indicators, and other field devices in process automation environments. Typical applications include emergency shutdown actuation, process valve control, and alarm annunciation in oil & gas, chemical, power generation, and pharmaceutical industries where high availability and reliability are paramount.
Q: What is the output current per channel?
A: Each channel can supply up to 2A at 24V DC.
Q: What type of output switching is used?
A: Electronic switching (high-side) is used for all 8 channels.
Q: Is this module suitable for redundant systems?
A: Yes, it supports H-System redundant configurations with S7-410 controllers.
Q: What diagnostics are available?
A: Comprehensive per-channel diagnostics including short circuit and overload detection.
Q: What BaseUnit is required?
A: An ET 200SP HA specific Base Unit must be used
FAQ
.
Siemens 6DL1134-6TB00-0HX1 | |
SIMATIC ET 200SP HA | Ex-AI 2xI 2-Wire HART, suitable for BaseUnit type X1, CC51, channel diagnostics, 16-bit, +/-0.3% | |
Feature | Specification |
Product type designation | Ex-AI 2xI 2-wire HART |
Firmware version | V1.0 |
FW update possible | Yes |
Usable BaseUnits | BU type X1 |
I&M data | Yes; I&M0 to I&M3 |
Engineering with STEP 7 TIA Portal | V16 |
Current consumption (rated value) | 74 mA |
Number of analog inputs for current measurement | 2; Differential inputs |
Input ranges (rated values), 0 to 20 mA | Yes |
Input ranges (rated values), 4 mA to 20 mA | Yes; 15 bit + sign |
Input resistance (4 mA to 20 mA) | 400 ohm |
Cycle time (all channels), min. | 3 ms |
Measurement principle | Integrating (Sigma-Delta) |
HART protocol | Yes |
Basic error limit at 25 °C, current | 0.2 % |
Operational error limit overall temperature range, current | 0.3 % |
Linearity error | 0.01 % |
Temperature error | 0.005 %/K |
Encoder supply 24 V | Yes; short-circuit protection |
Diagnostic alarm | Yes |
Limit value alarm | Yes |
Wire break | Yes; channel by channel |
Short-circuit | Yes; channel by channel |
Ex(i) characteristics for IIC: Uo | 26 V max. |
Ex(i) characteristics for IIC: Io | 93 mA max. |
Ex(i) characteristics for IIC: Po | 605 mW max. |
DIAG LED | Yes; green/red |
Channel status display | Yes; green LED |
Potential separation between channels and backplane bus | Yes |
Ambient temperature horizontal installation | -40 to 70 °C |
Width | 20 mm |
Height | 73 mm |
Depth | 58 mm |
Weight, approx. | 55 g |