The Siemens SIMATIC ET 200SP HA IM 134-6 JH (6DL1134-6JH00-0PH1) is a PROFIBUS DP interface module serving as the head station for the ET 200SP High Availability distributed I/O system. It provides the communication gateway between the I/O modules and the PROFIBUS DP network, enabling reliable data exchange with S7-410 series controllers in brownfield applications where PROFIBUS is the established fieldbus standard. The module supports HSR (High Speed Redundancy) for seamless failover in redundant configurations. Ideal for process automation retrofit and upgrade projects in oil & gas, chemical, and power generation plants that maintain PROFIBUS DP infrastructure while upgrading to HA-grade I/O systems.
Q: What fieldbus does this interface module use?
A: It uses PROFIBUS DP for communication with the controller.
Q: When should I choose PROFIBUS over PROFINET?
A: Choose PROFIBUS for brownfield/retrofit projects where existing PROFIBUS DP infrastructure is in place.
Q: Does this module support redundancy?
A: Yes, it supports HSR redundancy for high availability configurations.
Q: Is it compatible with PROFINET?
A: No. For PROFINET, use the IM 134-6 GH (6DL1134-6GH00-0PH1) version instead.
Q: What controllers are compatible?
A: It is designed for S7-410 series controllers in process automation
FAQ
.
Siemens 6DL1134-6JH00-0PH1 | |
SIMATIC ET 200SP HA | AI 16xTC/8xRTD 2-/3-/4-wire HA, suitable for terminal block H1, M1, CC00, channel diagnostics, 16-bit, +/-0.05% | |
Feature | Specification |
Product type designation | AI 16xTC/8xRTD 2/3/4-wire HA |
Firmware version | V1.1 |
FW update possible | Yes |
Usable terminal block | type H1, M1, N0, H0, M0 |
Color code for module-specific color-coded label | CC00 |
I&M data | Yes; I&M0 to I&M3 |
Engineering with STEP 7 TIA Portal | V16 |
Rated supply voltage (DC) | 24 V |
Permissible range, lower limit (DC) | 19.2 V |
Permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Current consumption (rated value) | 75 mA |
Number of analog inputs for thermocouple measurement | 16 |
Number of analog inputs for RTD measurement | 8 |
Thermocouple types | B, C, E, J, K, L, N, R, S, T, U, TXK/TXK(L) |
RTD types | Cu 10, Ni 100/120/200/500/1000, LG-Ni 1000, Pt 100/200/500/1000 |
Resistance ranges | 0-150/300/600/3000/6000 ohm, PTC |
Redundancy capability | Yes; With TB type M1 |
Basic error limit at 25 °C | 0.05 % |
Linearity error | 0.01 % |
Temperature error | 0.005 %/K |
Diagnostic alarm | Yes |
Limit value alarm | Yes |
Wire break | Yes; channel by channel |
DIAG LED | Yes; green/red |
Channel status display | Yes; green LED |
Potential separation between channels and backplane bus | Yes |
Isolation tested with | 1500 V DC/1 min, type test |
Ambient temperature horizontal installation | -40 to 70 °C |
Width | 22.5 mm |
Height | 115 mm |
Depth | 138 mm |
Weight, approx. | 170 g |