| Availability: | |
|---|---|
Siemens PLCs SIMATIC S7-300 FM352-5 with NPN 6ES7352-5AH01-0AE0
Siemens PLC Controller Module LOGO Series
We can Supply Siemens automation parts,such as Siemens PLC,Siemens Servo Motor,Siemens HMI,Siemens VFD and So on,
| Article number | 6ES7352-5AH01-0AE0 | 6ES7352-5AH11-0AE0 |
| FM 352-5, Boolean Processor 12DE/8DA | FM 352-5 PNP, Boolean Processor 12DI/8DO | |
| Supply voltage | ||
| Load voltage L+ | ||
| ● Rated value (DC)
| 24 V | 24 V |
| ● permissible range, lower limit (DC)
| 20.4 V | 20.4 V |
| ● permissible range, upper limit (DC)
| 28.8 V | 28.8 V |
| ● Reverse polarity protection
| Yes | Yes |
| Input current | ||
| from load voltage1L+, max. | 150 mA; typ. 60 mA | 150 mA; typ. 60 mA |
| from load voltage 2L+ (without load), max. | 200 mA; typ. 60 mA, DI/DO supply | 200 mA; typ. 60 mA, DI/DO supply |
| from load voltage 3L+ (with encoder), max. | 600 mA; typ. 80 mA plus encoder supply | 600 mA; typ. 80 mA plus encoder supply |
| from load voltage 3L+ (without load), max. | 200 mA; typ. 80 mA | 200 mA; typ. 80 mA |
| from backplane bus 5 V DC, typ. | 135 mA | 135 mA |
| Encoder supply | ||
| 5 V encoder supply | ||
| ● 5 V
| Yes | Yes |
| ● Short-circuit protection
| Yes; Electronic overload protection; no protection on applying a normal or counter voltage. | Yes; Electronic overload protection; no protection on applying a normal or counter voltage. |
| ● Output current, max.
| 250 mA | 250 mA |
| 24 V encoder supply | ||
| ● 24 V
| Yes | Yes |
| ● Short-circuit protection
| Yes; Overvoltage and overheating protection if overloaded; diagnostics if output reaches temperature limit; no protection on applying a normal or counter voltage | Yes; Overvoltage and overheating protection if overloaded; diagnostics if output reaches temperature limit; no protection on applying a normal or counter voltage |
| ● Output current, max.
| 400 mA | 400 mA |
| Power loss | ||
| Power loss, typ. | 6.5 W | 6.5 W |
| Memory | ||
| Type of memory | RAM | RAM |
| Memory size | 128 kbyte; required for operation, MMC | 128 kbyte; required for operation, MMC |
| Digital inputs | ||
| Number of digital inputs | 8; Standard and up to 12 with 24 V DC encoder inputs as digital inputs | 8; Standard and up to 12 with 24 V DC encoder inputs as digital inputs |
| Input voltage | ||
| ● Rated value (DC)
| 24 V | 24 V |
| ● for signal “0”
| -30 to +5 V | -30 to +5 V |
| ● for signal “1”
| +11 to +30V | +11 to +30V |
| Input current | ||
| ● for signal “0”, max. (permissible quiescent current)
| 1.5 mA | 1.5 mA |
| ● for signal “1”, typ.
| 3.8 mA | 3.8 mA |
| Input delay (for rated value of input voltage) | ||
| ● Input frequency (with a time delay of 0.1 ms), max.
| 200 kHz | 200 kHz |
| ● programmable digital filter delay
| None, 5 µs, 10 µs, 15 µs, 20 µs, 50 µs, 1.6 ms | None, 5 µs, 10 µs, 15 µs, 20 µs, 50 µs, 1.6 ms |
| ● Minimum pulse width for program reactions
| 1 µs, 5 µs, 10 µs, 15 µs, 20 µs, 50 µs, 1,6 ms | 1 µs, 5 µs, 10 µs, 15 µs, 20 µs, 50 µs, 1,6 ms |
| for standard inputs | ||
| — at “0” to “1”, max.
| 3 µs; typ. 1.5 µs | 3 µs; typ. 1.5 µs |
| Cable length | ||
| ● shielded, max.
| 600 m | 600 m |
| ● unshielded, max.
| 100 m; Shielded cable recommended if filtering delay is set to less than 1.6 ms | 100 m; Shielded cable recommended if filtering delay is set to less than 1.6 ms |
| Digital outputs | ||
| Number of digital outputs | 8 | 8 |
| Current-sinking | Yes | No |
| Current-sourcing | No | Yes |
| Short-circuit protection | Yes; Overvoltage protection, thermal protection | Yes; Overvoltage protection, thermal protection |
| ● Response threshold, typ.
| 1.7 to 3.5 A | 1.7 to 3.5 A |
| Limitation of inductive shutdown voltage to | 2M -45 V typ., (-40 V to -55 V); comment: no protection against inductive kickback >55 mJ | 2M -45 V typ., (-40 V to -55 V); comment: no protection against inductive kickback >55 mJ |