| Availability: | |
|---|---|
Siemens PLCs SIMATIC S7 Analog input SM 336 Module 6ES7336-4GE00-0AB0
Siemens PLC Controller Module LOGO Series
We can Supply Siemens automation parts,such as Siemens PLC,Siemens Servo Motor,Siemens HMI,Siemens VFD and So on,
| Article number | 6ES7336-4GE00-0AB0 |
| SM 336, f.AI 6 X 0/4 … 20mA HART | |
| Supply voltage | |
| Rated value (DC) | 24 V |
| Reverse polarity protection | Yes |
| Load voltage L+ | |
| ● Rated value (DC)
| 24 V |
| ● Reverse polarity protection
| Yes |
| Input current | |
| From power supply L+, typ. | 150 mA |
| from backplane bus 5 V DC, max. | 90 mA |
| Power loss | |
| Power loss, typ. | 4.5 W |
| Analog inputs | |
| Number of analog inputs | 6 |
| permissible input current for current input (destruction limit), max. | 40 mA |
| Input ranges | |
| ● Voltage
| No |
| ● Current
| Yes |
| ● Thermocouple
| No |
| ● Resistance thermometer
| No |
| ● Resistance
| No |
| Input ranges (rated values), currents | |
| ● 0 to 20 mA
| Yes |
| — Input resistance (0 to 20 mA)
| 150 Ω; typ. 150 ohms max. 175 ohms |
| ● 4 mA to 20 mA
| Yes |
| — Input resistance (4 mA to 20 mA)
| 150 Ω; typ. 150 ohms max. 175 ohms |
| Cable length | |
| ● shielded, max.
| 1 000 m |
| Analog value generation for the inputs | |
| Integration and conversion time/resolution per channel | |
| ● Resolution with overrange (bit including sign), max.
| 16 bit; 15 bit + sign |
| ● Integration time (ms)
| 20 ms @ 50 Hz, 16.7 ms @ 60 Hz |
| ● Interference voltage suppression for interference frequency f1 in Hz
| f=n x (f1 ±0.5 %) |
| Encoder | |
| Connection of signal encoders | |
| ● for current measurement as 2-wire transducer
| Yes |
| ● for current measurement as 4-wire transducer
| Yes |
| Errors/accuracies | |
| Operational error limit in overall temperature range | |
| ● Current, relative to input range, (+/-)
| 0.2 %; 40 µA |
| Basic error limit (operational limit at 25 °C) | |
| ● Current, relative to input range, (+/-)
| 0.1 % |
| Interrupts/diagnostics/status information | |
| Diagnostics function | Yes |
| Alarms | |
| ● Diagnostic alarm
| Yes |
| Diagnoses | |
| ● Diagnostic information readable
| Yes |
| Diagnostics indication LED | |
| ● Fail-safe operation
| Yes |
| ● Group error SF (red)
| Yes |
| ● Encoder supply Vs (green)
| No |
| Potential separation | |
| Potential separation analog inputs | |
| ● between the channels
| Yes |
| ● between the channels and backplane bus
| Yes |
| ● between the channels and the power supply of the electronics
| Yes |
| Isolation | |
| Isolation tested with | 370V for 1 min |
| Standards, approvals, certificates | |
| Highest safety class achievable in safety mode | |
| ● acc. to EN 954
| 4 |
| ● Performance level according to ISO 13849-1
| e |
| ● SIL acc. to IEC 61508
| SIL 3 |
| Connection method | |
| required front connector | 20-pin |
| Dimensions | |
| Width | 40 mm |
| Height | 125 mm |
| Depth | 120 mm |
| Weights | |
| Weight, approx. | 350 g |