| Availability: | |
|---|---|
6DL1134-6AF00-0PH1
Siemens
The Siemens SIMATIC ET 200SP HA DI 16xNAMUR HA (6DL1134-6AF00-0PH1) is a 16-channel digital input module for the ET 200SP High Availability distributed I/O system, specifically designed for safety-related applications. It accepts NAMUR proximity sensor signals and standard 24V DC inputs, with parameterizable input delay from 0.1 ms to 20 ms. Comprehensive diagnostics include wire break and short circuit to L+ detection per channel. Select channels support fast counting functions, making it versatile for both standard monitoring and pulse counting applications. Commonly used for valve position feedback and safety interlock monitoring in emergency shutdown systems, fire & gas systems, and burner management applications in oil & gas, chemical, and power generation industries.
Q: What sensor types are compatible?
A: NAMUR sensors (intrinsic safety) and 24V DC digital inputs, depending on configuration and Base Unit.
Q: Is this module suitable for safety applications?
A: Yes, it is specifically designed for use in safety-related applications such as valve position feedback.
Q: Can this module perform counting functions?
A: Yes, fast counting and counter functions are available on select channels.
Q: What is the input delay range?
A: The input delay is parameterizable from 0.1 ms to 20 ms.
Q: What diagnostics are available?
A: Wire break detection and short circuit to L+ detection are available per channel
FAQ
.
Siemens 6DL1134-6AF00-0PH1 | |
SIMATIC ET 200SP HA | AI 8xU/I/TC/4xRTD 2-/3-/4-wire HA, suitable for terminal block H1, N0, H0, CC00, channel diagnostics | |
Feature | Specification |
Product type designation | AI 8xU/I/TC/4xRTD 2/3/4-wire HA |
Firmware version | V1.0 |
FW update possible | Yes |
Usable terminal block | type H1, N0, H0 |
Color code for module-specific color-coded label | CC00 |
I&M data | Yes; I&M0 to I&M3 |
Engineering with STEP 7 TIA Portal | V18 |
Rated supply voltage (DC) | 24 V |
Permissible range, lower limit (DC) | 19.2 V |
Permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Current consumption (rated value) | 220 mA |
Number of analog inputs for current measurement | 8 |
Number of analog inputs for voltage measurement | 8 |
Number of analog inputs for thermocouple measurement | 8 |
Number of analog inputs for RTD measurement | 4 |
Input ranges (rated values), 4 mA to 20 mA | Yes; 15 bit |
Input ranges (rated values), +/-10 V | Yes; 16 bit incl. sign |
Thermocouple types supported | B, C, E, J, K, L, N, R, S, T, U, TXK/TXK(L) |
RTD types supported | Cu 10/50/100, Ni 100/1000, LG-Ni 1000, Pt 100/1000 |
Basic error limit at 25 °C, current | 0.3 % |
Linearity error | 0.02 % |
Temperature error | 0.005 %/K |
Diagnostic alarm | Yes |
Limit value alarm | Yes |
Wire break | Yes |
DIAG LED | Yes; green/red |
Potential separation between channels and backplane bus | Yes |
Isolation tested with | 1500 V DC/1 min, type test |
Ambient temperature horizontal installation | -40 to 70 °C |
Width | 22.5 mm |
Height | 115 mm |
Depth | 138 mm |
Weight, approx. | 170 g |
autocoberry.com — We supply whatever you need, with the price far lower than the market rates. | |