| Availability: | |
|---|---|
6DL1133-6EW00-0PH1
Siemens
The Siemens SIMATIC ET 200SP HA AQ 8xI HART HA (6DL1133-6EW00-0PH1) is an 8-channel analog output module for the ET 200SP High Availability distributed I/O system. It provides configurable voltage and current outputs per channel with integrated HART communication and 16-bit resolution. The module features extensive diagnostics including wire break, short circuit, and supply voltage monitoring, and complies with NAMUR NE 43 standards. Output behavior on communication loss is configurable to either hold the last value or switch to a predefined substitute value. Designed for redundant H-System configurations with S7-410 controllers, it is ideal for controlling actuators, control valves, and positioners in oil & gas, chemical, and power generation process plants.
Q: What output types are supported?
A: Both voltage and current outputs are supported, configurable per channel.
Q: Is HART communication available on all channels?
A: Yes, integrated HART communication is available on all 8 channels.
Q: What happens if communication with the PLC is lost?
A: Output behavior is configurable - either hold the last value or switch to a substitute value.
Q: Is this module NAMUR compliant?
A: Yes, it complies with NAMUR NE 43 standards for analog output signals.
Q: Can this module be used in safety applications?
A: Yes, the module is designed for safety-rated systems when properly configured
FAQ
.
Siemens 6DL1133-6EW00-0PH1 | |
SIMATIC ET 200SP HA | AI-DI16/DQ16x24VDC HART HA, suitable for terminal block H1, M1, CC00, channel diagnostics, configurable I/O | |
Feature | Specification |
Product type designation | AI-DI16/DQ16x24VDC HART HA |
Firmware version | V1.0 |
FW update possible | Yes |
Usable terminal block | type H1, M1, N0, H0, M0 |
Color code for module-specific color-coded label | CC00 |
I&M data | Yes; I&M0 to I&M3 |
Engineering with STEP 7 TIA Portal | V16 |
Rated supply voltage (DC) | 24 V |
Permissible range, lower limit (DC) | 19.2 V |
Permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Current consumption (rated value) | 200 mA |
Number of analog inputs for current measurement | 4; 4 to 20 mA HART |
Number of digital inputs | 16 |
Number of digital outputs | 16; 0.5 A each |
Input ranges (rated values), 4 mA to 20 mA | Yes; 16 bit incl. sign |
HART protocol | Yes |
Basic error limit at 25 °C, current | 0.1 % |
Diagnostic alarm | Yes |
Limit value alarm | Yes |
Wire break | Yes |
Short-circuit | Yes |
DIAG LED | Yes; green/red |
Channel status display | Yes; green LED |
Potential separation between channels and backplane bus | Yes |
Isolation tested with | 1500 V DC/1 min, type test |
Ambient temperature horizontal installation | -40 to 70 °C |
Width | 22.5 mm |
Height | 115 mm |
Depth | 138 mm |
Weight, approx. | 170 g |
autocoberry.com — We supply whatever you need, with the price far lower than the market rates. | |