| Availability: | |
|---|---|
Siemens PLCs SIMATIC S7-300 Counter module FM 350-1 6ES7350-1AH03-0AE0
We can Supply Siemens automation parts,such as Siemens PLC,Siemens Servo Motor,Siemens HMI,Siemens VFD and So on,
| Article number | 6ES7350-1AH03-0AE0 |
| FM350-1, counter mod. up to 500KHZ | |
| Supply voltage | |
| Auxiliary voltage 1L+, load voltage 2L+ | |
| ● Rated value (DC)
| 24 V |
| ● permissible range, lower limit (DC)
| 20.4 V; Dynamic 18.5 V |
| ● permissible range, upper limit (DC)
| 28.8 V; dynamic 30.2 V |
| Input current | |
| from load voltage 1L+ (without load), max. | 40 mA |
| from backplane bus 5 V DC, max. | 160 mA |
| Encoder supply | |
| 5 V encoder supply | |
| ● 5 V
| Yes; 5.2 V ±2 % |
| ● Output current, max.
| 300 mA |
| 24 V encoder supply | |
| ● 24 V
| Yes; 1L+ (-3 V) |
| ● Output current, max.
| 400 mA |
| Power loss | |
| Power loss, typ. | 4.5 W |
| Digital inputs | |
| Number of digital inputs | 3 |
| Functions | 1 for gate start, 1 for gate stop, 1 for setting the counter |
| Input voltage | |
| ● for signal “0”
| -28.8 … +5V |
| ● for signal “1”
| +11 to +28.8V |
| Input current | |
| ● for signal “1”, typ.
| 9 mA |
| Digital outputs | |
| Number of digital outputs | 2 |
| Short-circuit protection | Yes; Clocked electronically |
| Limitation of inductive shutdown voltage to | 2L+ (-39 V) |
| Output voltage | |
| ● for signal “0”, max.
| 3 V |
| ● for signal “1”, min.
| 2L+ (-1,5 V) |
| Output current | |
| ● for signal “1” rated value
| 0.5 A |
| ● for signal “1” permissible range for 0 to 60 °C, min.
| 5 mA |
| ● for signal “1” permissible range for 0 to 60 °C, max.
| 0.6 A |
| Output delay with resistive load | |
| ● “0” to “1”, max.
| 300 µs |
| Encoder | |
| Connectable encoders | |
| ● Incremental encoder (symmetrical)
| Yes; With 2 pulse trains offset by 90° |
| ● Incremental encoder (asymmetrical)
| Yes |
| ● 24 V initiator
| Yes |
| ● 24 V directional element
| Yes; 1 pulse train, 1 direction level |
| Counter | |
| Number of counter inputs | 1; 32 bit or ±31 bit |
| Counter input 5 V | |
| ● Type
| RS 422 |
| ● Terminating resistor
| 220 Ω |
| ● Differential input voltage
| 1,3 V |
| ● Counting frequency, max.
| 500 kHz |
| Counter input 24 V | |
| ● Input voltage for signal “0”
| -28.8 … +5V |
| ● Input voltage for signal “1”
| +11 to +28.8V |
| ● Input current for signal “1”, typ.
| 9 mA |
| ● Counting frequency, max.
| 200 kHz |
| ● Minimum pulse width
| 2.5 µs |
| Potential separation | |
| Potential separation digital inputs | |
| ● between the channels and backplane bus
| Yes; Optocoupler |
| Potential separation digital outputs | |
| ● between the channels and backplane bus
| Yes; Optocoupler |
| Potential separation counter | |
| ● between the channels and backplane bus
| Yes; Optocoupler |
| Isolation | |
| Isolation tested with | 500 V |
| Connection method | |
| required front connector | 1x 20-pin |
| Dimensions | |
| Width | 40 mm |
| Height | 125 mm |
| Depth | 120 mm |
| Weights | |
| Weight, approx. | 250 g |