Availability: | |
---|---|
Product Details
16 and 32-channel digital input modules
We are First Class Siemens Supplier,siemens plc dealer and Siemens plc distributor in China.
We can Supply Siemens automation parts,such as Siemens PLC,Siemens Servo Motor,Siemens HMI,Siemens VFD and So on,
100% Original and new,In stock by Siemens Automation
Delivery time: Ready in stock and 1 days for ship out
MOQ: 1pcs
Specification
Article number | 6ES7521-1BH10-0AA0 | 6ES7521-1BL10-0AA0 |
S7-1500, DI 16x24VDC BA | S7-1500, DI 32x24VDC BA | |
General information | ||
Product type designation | DI 16 x 24 V DC BA | DI 32x24VDC BA |
HW functional status | FS01 | FS01 |
Firmware version | V1.0.0 | V1.0.0 |
● FW update possible | Yes | Yes |
Product function | ||
● I&M data | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 |
● Isochronous mode | No | No |
● Prioritized startup | Yes | Yes |
Engineering with | ||
● STEP 7 TIA Portal configurable/integrated from version | V13 / V13 | V13 / V13 |
● STEP 7 configurable/integrated from version | V5.5 SP3 / – | V5.5 SP3 / – |
● PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 | V1.0 / V5.1 |
● PROFINET from GSD version/GSD revision | V2.3 / – | V2.3 / – |
Operating mode | ||
● DI | Yes | Yes |
● Counter | No | No |
● MSI | Yes | Yes |
Supply voltage | ||
Rated value (DC) | 24 V | 24 V |
permissible range, lower limit (DC) | 20.4 V | 20.4 V |
permissible range, upper limit (DC) | 28.8 V | 28.8 V |
Power | ||
Power available from the backplane bus | 1.05 W | 1.05 W |
Power loss | ||
Power loss, typ. | 1.8 W | 3 W |
Digital inputs | ||
Number of digital inputs | 16 | 32 |
Digital inputs, parameterizable | No | No |
Source/sink input | P-reading | P-reading |
Input characteristic curve in accordance with IEC 61131, type 3 | Yes | Yes |
Input voltage | ||
● Rated value (DC) | 24 V | 24 V |
— 24 V DC | Yes | Yes |
● for signal “0” | -30 to +5 V | -30 to +5 V |
● for signal “1” | +11 to +30V | +11 to +30V |
Input current | ||
● for signal “1”, typ. | 2.7 mA | 2.7 mA |
Input delay (for rated value of input voltage) | ||
for standard inputs | ||
— parameterizable | No | No |
— at “0” to “1”, min. | 3 ms | 3 ms |
— at “0” to “1”, max. | 4 ms | 4 ms |
— at “1” to “0”, min. | 3 ms | 3 ms |
— at “1” to “0”, max. | 4 ms | 4 ms |
for interrupt inputs | ||
— parameterizable | No | No |
for technological functions | ||
— parameterizable | No | No |
Cable length | ||
● shielded, max. | 1 000 m | 1 000 m |
● unshielded, max. | 600 m | 600 m |
Encoder | ||
Connectable encoders | ||
● 2-wire sensor | Yes | Yes |
— permissible quiescent current (2-wire sensor), max. | 1.5 mA | 1.5 mA |
Interrupts/diagnostics/status information | ||
Diagnostics function | No | No |
Alarms | ||
● Diagnostic alarm | No | No |
● Hardware interrupt | No | No |
Diagnoses | ||
● Monitoring the supply voltage | No | No |
● Wire-break | No | No |
● Short-circuit | No | No |
Diagnostics indication LED | ||
● RUN LED | Yes; green LED | Yes; green LED |
● ERROR LED | Yes; red LED | Yes; red LED |
● Monitoring of the supply voltage (PWR-LED) | No | No |
● Channel status display | Yes; green LED | Yes; green LED |
● for channel diagnostics | No | No |
● for module diagnostics | No | No |
Potential separation | ||
Potential separation channels | ||
● between the channels | No | No |
● between the channels, in groups of | 16 | 16 |
● between the channels and backplane bus | Yes | Yes |
● between the channels and the power supply of the electronics | No | |
Isolation | ||
Isolation tested with | 707 V DC (type test) | 707 V DC (type test) |
Standards, approvals, certificates | ||
Suitable for safety functions | No | No |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | 0 °C | 0 °C |
● horizontal installation, max. | 60 °C | 60 °C |
● vertical installation, min. | 0 °C | 0 °C |
● vertical installation, max. | 40 °C | 40 °C |
Altitude during operation relating to sea level | ||
● Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
Dimensions | ||
Width | 25 mm | 25 mm |
Height | 147 mm | 147 mm |
Depth | 129 mm | 129 mm |
Weights | ||
Weight, approx. | 230 g | 260 g |