| Article number | 6ES7522-1BH01-0AB0 | 6ES7522-1BL01-0AB0 | 6ES7522-1BF00-0AB0 | 6ES7522-5EH00-0AB0 |
| S7-1500, DQ 16x24V DC/0.5A HF | S7-1500, DQ 32x24VDC/0.5A HF | S7-1500, DQ 8x24VDC/2A HF | S7-1500, DQ 16×24…48VUC/125VDC/0.5A ST | |
| General information | ||||
| Product type designation | DQ 16x24VDC/0.5A HF | DQ 32x24VDC/0.5A HF | DQ 8x24VDC/2A HF | DQ 16×24 … 48 V UC/125 V DC/0.5 A ST |
| HW functional status | From FS02 | From FS02 | FS03 | FS02 |
| Firmware version | V1.1.0 | V1.1.0 | V2.2.0 | V1.0.0 |
| ● FW update possible
| Yes | Yes | Yes | |
| Product function | ||||
| ● I&M data
| Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 |
| ● Isochronous mode
| Yes | Yes | No | No |
| ● Prioritized startup
| Yes | Yes | Yes | Yes |
| Engineering with | ||||
| ● STEP 7 TIA Portal configurable/integrated from version
| V13 SP1 / – | V13 SP1 / – | V13 SP1 / – | V13 SP1 / – |
| ● STEP 7 configurable/integrated from version
| V5.5 SP3 / – | V5.5 SP3 / – | ||
| ● PROFIBUS from GSD version/GSD revision
| V1.0 / V5.1 | V1.0 / V5.1 | V1.0 / V5.1 | V1.0 / V5.1 |
| ● PROFINET from GSD version/GSD revision
| V2.3 / – | V2.3 / – | V2.3 / – | V2.3 / – |
| Operating mode | ||||
| ● DQ
| Yes | Yes | Yes | Yes |
| ● DQ with energy-saving function
| No | No | Yes; with an application | No |
| ● PWM
| No | No | Yes | No |
| ● Cam control (switching at comparison values)
| No | No | No | No |
| ● Oversampling
| No | No | No | No |
| ● MSO
| Yes | Yes | Yes | Yes |
| ● Integrated operating cycle counter
| Yes | Yes | Yes | No |
| Supply voltage | ||||
| Rated value (DC) | 24 V | 24 V | 24 V | |
| permissible range, lower limit (DC) | 20.4 V | 20.4 V | 20.4 V | |
| permissible range, upper limit (DC) | 28.8 V | 28.8 V | 28.8 V | |
| Reverse polarity protection | Yes; through internal protection with 7 A per group | Yes; through internal protection with 7 A per group | Yes; through internal protection with 10 A per group | |
| Input current | ||||
| Current consumption, max. | 30 mA | 60 mA | 40 mA; 20 mA per group, no output is activated. | |
| Output voltage | ||||
| Rated value (DC) | 24 V | 24 V | 24 V | 24 V; 48 V, 125 V |
| Rated value (AC) | 24 V; 48 V (50 – 60 Hz) | |||
| Power | ||||
| Power available from the backplane bus | 1.1 W | 1.1 W | 0.9 W | 2 W |
| Power loss | ||||
| Power loss, typ. | 2 W | 3.5 W | 5.6 W; 6.8 W for PWM operation | 3.8 W |
| Digital outputs | ||||
| Type of digital output | Transistor | Transistor | Transistor | Transistor |
| Number of digital outputs | 16 | 32 | 8 | 16 |
| Current-sinking | Yes | |||
| Current-sourcing | Yes | Yes | Yes | Yes |
| Digital outputs, parameterizable | Yes | Yes | Yes | Yes |
| Short-circuit protection | Yes; Clocked electronically | Yes; Clocked electronically | Yes | |
| ● Response threshold, typ.
| 1 A | 1 A | 3 A | |
| Limitation of inductive shutdown voltage to | L+ (-53 V) | L+ (-53 V) | -17 V | 200 V (suppressor diode) |
| Controlling a digital input | Yes | Yes | Yes | Yes |
| Digital output functions, parameterizable | ||||
| ● Freely usable digital output
| Yes | |||
| ● PWM output
| Yes | |||
| — Number, max.
| 2 | |||
| — Cycle duration, parameterizable
| Yes; 2 … 100 ms continuous | |||
| — ON period, min.
| 0 % | |||
| — ON period, max.
| 100 % | |||
| — Resolution of the duty cycle
| 0.1 % | |||
| — Minimum pulse duration
| 300 µs | |||
| Switching capacity of the outputs | ||||
| ● with resistive load, max.
| 0.5 A | 0.5 A | 0.5 A | |
| ● on lamp load, max.
| 5 W | 5 W | 10 W | 40 W; At 125 V DC, 10 W at 48 V UC, 5 W at 24 V UC |
| Load resistance range | ||||
| ● lower limit
| 48 Ω | 48 Ω | 12 Ω | |
| ● upper limit
| 12 kΩ | 12 kΩ | 4 kΩ | |
| Output voltage | ||||
| ● for signal “1”, min.
| L+ (-0.8 V) | L+ (-0.8 V) | L+ (-0.8 V) | L+ (-1.0 V) |
| Output current | ||||
| ● for signal “1” rated value
| 0.5 A | 0.5 A | 2 A | 0.5 A |
| ● for signal “1” permissible range, max.
| 0.5 A | 0.5 A | 2.4 A; note derating specification for PWM operation | 0.6 A |
| ● for signal “0” residual current, max.
| 0.5 mA | 0.5 mA | 0.5 mA | |
| Output delay with resistive load | ||||
| ● “0” to “1”, typ.
| 80 µs | |||
| ● “0” to “1”, max.
| 100 µs | 100 µs | 100 µs | 5 ms |
| ● “1” to “0”, typ.
| 300 µs | |||
| ● “1” to “0”, max.
| 500 µs | 500 µs | 500 µs | 5 ms |
| Parallel switching of two outputs | ||||
| ● for logic links
| Yes | Yes | Yes | Yes |
| ● for uprating
| No | No | No | No |
| ● for redundant control of a load
| Yes | Yes | Yes | Yes |