Specification
Article number | 6ES7522-5HF00-0AB0 | 6ES7522-5HH00-0AB0 | 6ES7522-5FF00-0AB0 | 6ES7522-5FH00-0AB0 |
S7-1500, DQ 8x230VAC/5A ST (Relay) | S7-1500, DQ 16x230VAC/2A ST (Relay) | S7-1500, DQ 8x230VAC/2A ST (Triac) | S7-1500, DQ 16x230VAC/1A ST (Triac) | |
General information | ||||
Product type designation | DQ 8×230 V AC/5 A ST (relay) | DQ 16x 230 V AC/2 A ST (relay) | DQ 8×230 V AC/2A ST (triac) | DQ 16x230VAC/1A ST (Triac) |
HW functional status | From FS02 | From FS02 | FS01 | FS01 |
Firmware version | V2.1.0 | V1.1.0 | V2.0.0 | V1.0.0 |
● FW update possible | Yes | Yes | Yes | Yes |
Product function | ||||
● I&M data | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 |
● Isochronous mode | No | No | No | No |
● Prioritized startup | Yes | Yes | Yes | Yes |
Engineering with | ||||
● STEP 7 TIA Portal configurable/integrated from version | V12 / V12 | V13 SP1 / – | V12 / V12 | V13 SP1 / – |
● STEP 7 configurable/integrated from version | V5.5 SP3 / – | V5.5 SP3 / – | V5.5 SP3 / – | V5.5 SP3 / – |
● PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 | V1.0 / V5.1 | V1.0 / V5.1 | V1.0 / V5.1 |
● PROFINET from GSD version/GSD revision | V2.3 / – | V2.3 / – | V2.3 / – | V2.3 / – |
Operating mode | ||||
● DQ | Yes | Yes | Yes | Yes |
● DQ with energy-saving function | No | No | No | No |
● PWM | No | No | No | No |
● Oversampling | No | No | No | No |
● MSO | Yes | Yes | Yes | Yes |
● Integrated operating cycle counter | Yes; FW V2.1.0 or higher | Yes; FW V1.1.0 or higher | ||
Supply voltage | ||||
Rated value (DC) | 24 V | 24 V | ||
permissible range, lower limit (DC) | 20.4 V | 20.4 V | ||
permissible range, upper limit (DC) | 28.8 V | 28.8 V | ||
Reverse polarity protection | Yes | Yes | ||
Input current | ||||
Current consumption, max. | 80 mA | 185 mA | ||
Output voltage | ||||
Rated value (AC) | 230 V; 24 V DC to 120 V DC / 24 V AC to 230 V AC | 230 V; 24 V DC to 120 V DC / 24 V AC to 230 V AC | 230 V; 120/230 V AC, 50/60 Hz | 230 V; 120/230 V AC, 50/60 Hz |
Power | ||||
Power available from the backplane bus | 0.8 W | 0.8 W | 0.9 W | 1.2 W |
Power loss | ||||
Power loss, typ. | 5 W | 5 W | 10.8 W | 11.1 W |
Digital outputs | ||||
Type of digital output | Relays | Relays | Triac | Triac |
Number of digital outputs | 8 | 16 | 8 | 16 |
Current-sinking | Yes | Yes | Yes | |
Current-sourcing | Yes | Yes | Yes | Yes |
Digital outputs, parameterizable | Yes | Yes | Yes | Yes |
Short-circuit protection | No | No | No | No |
● built-in fuse | 6.3 A melting fuse, slow-blow | 6.3 A melting fuse, slow-blow | ||
Controlling a digital input | possible | Yes | ||
Size of motor starters according to NEMA, max. | 5 | 5 | 5 | 4 |
Switching capacity of the outputs | ||||
● with resistive load, max. | 2 A | 1 A | ||
● on lamp load, max. | 1 500 W; 10 000 operating cycles | 50 W (230 V AC), 5 W (24 V DC) | 50 W | 50 W |
● Low energy/fluorescent lamps with electronic control gear | 10x 58 W (25 000 operating cycles) | |||
● Fluorescent tubes, conventionally compensated | 1x 58 W (25 000 operating cycles) | |||
● Fluorescent tubes, uncompensated | 10x 58 W (25 000 operating cycles) | |||
Output voltage | ||||
● for signal “1”, min. | L1 (-1.5 V) at maximum output current; L1 (-8.5 V) at minimum output current | L1 (-1.5 V) at maximum output current; L1 (-8.5 V) at minimum output current | ||
Output current | ||||
● for signal “1” rated value | 5 A | 2 A | 2 A | 1 A |
● for signal “1” permissible range, min. | 5 mA; 10 V | 10 mA; 10 V | 10 mA | 10 mA |
● for signal “1” permissible range, max. | 8 A; thermal continuous current | 2 A; thermal continuous current | 15 A; max. 1 AC cycle | 15 A; max. 1 AC cycle |
● for signal “0” residual current, max. | 0 A | 0 A | 2 mA | 2 mA |
Output delay with resistive load | ||||
● “0” to “1”, max. | 1 AC cycle | 1 AC cycle | ||
● “1” to “0”, max. | 1 AC cycle | 1 AC cycle | ||
Parallel switching of two outputs | ||||
● for logic links | Yes | Yes | No | No |
● for uprating | No | No | No | No |
● for redundant control of a load | Yes | Yes | Yes | Yes |
Switching frequency | ||||
● with resistive load, max. | 2 Hz | 1 Hz | 10 Hz | 10 Hz |
● with inductive load, max. | 0.5 Hz | 0.5 Hz | 0.5 Hz | 0.5 Hz |
● on lamp load, max. | 2 Hz | 1 Hz | 1 Hz | 1 Hz |
Total current of the outputs | ||||
● Current per channel, max. | 8 A; see additional description in the manual | 2 A; see additional description in the manual | 2 A; see additional description in the manual | 1 A; see additional description in the manual |
● Current per group, max. | 8 A; see additional description in the manual | 4 A; see additional description in the manual | 2 A; see additional description in the manual | 2 A; see additional description in the manual |
● Current per module, max. | 64 A; see additional description in the manual | 32 A; see additional description in the manual | 10 A; see additional description in the manual | 10 A; see additional description in the manual |